C-05830 Compact Micro IV™ Lead-Lag Sequencer

Description

  • Maintains facility main header temperature or pressure for efficient production and heating: eliminates variable energy supply and meets demand!
  • Universal applications: controls any model burner or boiler. Use Model C-05830 Compact Micro IV™ for up to six boilers. Model C-05810 Micro IV™ handles additional boilers with added features such as flue gas monitoring.
  • Sequencing with modulation for steam or hot water boilers and auxiliary boiler plant equipment.
  • On-Off, Low-High-Off or Full-modulation.
  • Time-based main header temperature or pressure control: fully factory-configured before shipment.
  • Fully Automatic control & burner interface.
  • Building Management (EMS) interface with ASCI-II and RS- 485 Modbus ports for remote control, data acquisition and SCADA systems.
  • Master set point tracking.
  • Real-time data acquisition including firing rates, lead boiler run time, pressures, and temperatures.
  • Bright Vacuum Fluorescent Display: 2 easy-to-read lines using engineering units.
  • Front panel operator interfaces include boiler ON lights, engineering unit displays of boiler operation functions, manual/auto/off switches, dedicated display of header temperature or pressure.
  • Five lead-boiler rotation modes: manual selection (via keypad entry); automatic rotation on a weekly basis; automatic rotation based on lead-boiler run time; or remote select with Modbus or switched inputs.
  • Night set-back/weekend skip: real-time clock for automatic set point reduction during lighter load periods.
  • Packaged systems ready for installation! Systems include field sensors and installation start-up instructions.